FLEXURAL STRENGTH, ICBO ES AC07 SEC. 3.22 &UBC STANDARD 15-5

Client: WEDGE-IT CO.

Date of test: november 10,2000

Type of Test: FlEXURAL STRENGTH, ICBO ES AC07 SECTION 3.22

AND UBC  STANDARD 15-5

REASON: TO VERIFY THE LOAD CAPACITY USING WEDGE-IT

LABORATORY NUMBER: 11609 RAMTECH LABORTATORIES INC.

TEST:

A series of comparative flexural strength tests have been conducted on the submitted WEDGE-IT tapered foam boards using Eagle Lite Tile flat shake roof tiles. The test was conducted in accordance with ICBO, ES Inc. AC 07 flexural strength test. The first flexural strength series (control) was conducted without any tapered foam board. The second series was conducted with 1-5/8 inch WEDGE-IT tapered foam board under the tile. The third series was conducted with 1-9/16 inch WEDGE-IT tapered foam board under the tile. All tiles used in the test program were identified as being manufactured with the same lot number and same manufacturer. Each of the three test series was conducted using a 4’ x 8’ test deck with the tiles being installed in a standard installation procedure with a 3” head lap. The loads were applied through a flat 2” x 4” positioned at the center of the test span as shown in UBC Standard 15-5.

FLEXURAL STRENGTH WITHOUT WEDGE-IT TAPERED FOAM BOARD (CONTROL)

Results: The average breaking load 250 pounds with no single load less than 225 pounds.

FLEXURAL STRENGTH WITH 1-9/16” WEDGE-IT TAPERED FOAM BOARD UNDERTILE

Results:  The average breaking load 575 pounds with no single load less than 510 pounds.

 

CONCLUSIONS:

Comment: The test data shows that the use of the WEDGE-IT foam boards Installed below the concrete tiles, more than double the flexural bearing loads. This fact should translate to greatly improved walkability on any tile roofing system using the WEDGE-IT Installation system.

Ramtech Laboratories, Inc. Reports are for the exclusive use of the client to whom they are addressed. Permission is granted to reproduce this Report provided it is reproduced entirely. The use of the name Ramtech Laboratories, Inc. in any advertising or related materials must have prior written approval.  Reports apply only to samples tested and are not necessarily indicative of the quality of apparently Identical or similar products. Ramtech Laboratories, Inc. is a recognized Testing Laboratory with the City of Los Angeles (RR23840) and the ICBO Evaluation Service, Inc. (TL-167)